Call Us : 0086 21 5032 3161、.0086 13816145342
|

My Site

Categories
PTAC package air conditioner Home > PTAC package air conditioner
PTAC package air conditioner
  • PTAC package air conditioner
  • PTAC package air conditioner
  • PTAC package air conditioner
  • PTAC package air conditioner
  • PTAC package air conditioner

PTAC package air conditioner

Item No.: YAPT-09DCN
PTAC stands for Package Terminal Air Conditioner. They're used a lot in the hospitality industry - you've probably stayed in a hotel that had them. A PTAC is a self-contained air conditioning unit that is installed through an outside wall rather than thro
$570.00
INQUIRY
PTAC  Package Terminal Air Conditioner.

A few "green" reasons to consider ptac air conditioners

In some cases, PTAC air conditioning units can be more energy efficient (and hence more "green") than traditional window unit air conditioners or central units. Here are 10 eco-friendly reasons you should consider a PTAC unit.
  • Many models have electronic temperature limits. You can set separate heating and cooling ranges to prevent the cost of extreme use.
  • If you're in the hospitality industry, you can order desk ready controls that allow you to turn units on when guests arrive, and then turn them off after they leave.
  • You can get PTAC units with energy efficiency ratios (EERs) . This will help you save on electricity.
  • Custom controls can be added for institutional uses (offices, schools, etc.) such as start / stop control that provides heating or A/C from a specified time in the morning to a specified time in the evening. This kind of control is connected to a central energy management system.
  • Morning warm-up control can be used in offices and schools to pre-warm rooms before peak demand electricity rates kick in. Pre-warming offices or classrooms ensures that when workers and / or students arrive, they aren't turning their units on at the same time during peak demand periods.
  • A "day reset" button can be used in conjunction with systems that are set to run during set hours, say 7 a.m. to 6 p.m. If anyone is around after the units shut off for the day, they can press a "day reset" button on their unit to continue having heat or A/C. This feature can also be programmed for weekend use.
  • Heating element lock-out is the cold weather counterpart to compressor lock-out. For example, on a cool (but not cold) winter day, heating elements on the south side of a building could have the elements locked out for a certain period of time while the heating elements on the north side of a building would continue to have operational heating elements due to their colder conditions.
  • Using a remote temperature sensor with a PTAC air conditioner allows temperature sensing on an internal wall for better temperature control than an on-unit sensor.
  • Cleanable, reusable filters keep dirt and lint off the coil. They can be easily removed, cleaned, and reinserted, making it easy for users to maximize the energy efficiency of their PTAC unit.
  • Technical specification : Seires name (Model range) R-22 50Hz Rev.0
    Model NO YAPT-09DCN YAPT-12DCN YAPT-15DCN YAPT-18DCN
    Power supply V/Ph/Hz 220-240V/1Ph/50Hz 220-240V/1Ph/50Hz 220-240V/1Ph/50Hz 220-240V/1Ph/50Hz
    Cooling Capacity    rated Btu/h 9500 12000 15000 18000
    Capacity  rated W 2800 3500 4396 5275
    Input            tested W 860 1080 1380 1730
    Rated current A 3.9 4.8 6.2 7.6
    EER Btu/h.W 11.10 11.00 10.87 10.40
    EER W/W 3.26 3.24 3.19 3.05
    Heating Capacity Btu/h 10000 10000 10000 10000
    Capacity W 3150 3150 3150 3150
    Input W 2800 2800 2800 2800
    Rated current A 15 15 15 15
    COP Btu/h.W 3.34 3.34 3.34 3.34
    COP W/W 0.98 0.98 0.98 0.98
    Moisture Removal l/h 1.41 1.41 1.41 1.83
    Operation Control   Auto Auto Auto Auto
    Indoor coil Number of row   2 2 3 3
    Fin spacing mm 1.6 1.6 1.8 1.8
    Fin material   Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium
    Tube outside diameter mm 7 7 7.94 7.94
    Tube material   Innergroove tube Innergroove tube Innergroove tube Innergroove tube
    Coil widthx height x depth mm 630x220x26.5 630x220x26.5 630x220x51.96 630x220x51.96
    Number of circuit   2 2 2 2
    Indoor fan motor Brand   / / / /
    Model   YSK30-4E24 YSK35-4E24 YSK35-4E24 YSK35-4E24
    Input W 30 35 40 40
    Output W 16 18 20 20
    Running current A 0.6 0.6 0.6 0.6
    Capacitor mF 4 4 4 4
    Speed (Hi/Lo) rpm 930/800 1134/930 1255/1134 1255/1134
    Indoor air flow (Hi/Lo) m3/h 550/450 680/550 775/680 775/680
    Indoor noise level (Hi/Lo) dB(A) 45/40 50/45 53/50 53/50
    Indoor dimension Unit (HxWxD) mm 530x900x215 530x900x215 530x900x215 530x900x215
    Outdoor coil Number of row   2 2 3 3
    Fin spacing mm 1.8 1.8 2.0 2.0
    Fin material   Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium
    Tube outside diameter mm 7.94 7.94 7.94 7.94
    Tube material   Innergroove tube Innergroove tube Innergroove tube Innergroove tube
    Coil width x height x depth mm 495X350X34.64 495X350X34.64 495X350X51.96 495X350X51.96
    Number of circuit   2 2 2 3
    Compressor Brand   Panasonic Panasonic Hitachi Hitachi
    Model   5RS092ZJB21 5RS102ZBC21 ASG133SDNB7AT ASG133SDNB7AT
    Type   Rotary Rotary Rotary Rotary
    Outdoor fan motor Brand   / / / /
    Model   YDK-35D-4-2 YDK-35D-4-2 YDK-35D-4-2 YDK-35D-4-2
    Input W 115 135 135 135
    Output W 30 35 35 35
    Running current A 0.16 0.16 0.16 0.16
    Capacitor mF 3 3 3 3
    Speed      ( hi/low) rpm 1350/1100 1350/1100 1350/1100 1350/1100
    Outdoor air flow m3/h 1100 1100 1100 1100
    Outdoor noise level dB(A) 72 72 72 72
    Outdoor dimension Unit (HxWxD) mm 385x745x310 385x745x310 385x745x310 385x745x310
    Unit dimension Packing (HxWxD) mm 567x973x600 567x973x600 567x973x600 567x973x600
    Unit weight Net kg 59 68 70 70
    Gross kg 65 74 76 76
    Refrigerant Type   R410a R410a R410a R410a
    Charge g 700 800 1100 1100
    Operation temperature range 16-35 16-35 16-35 16-35
    Ambient temperature range -7-42 -7-42 -7-42 -7-42
    Application area m2 16-30 26-38 35-50 40-56
    PRICE
    1* sample price  need research  and lab test , the cost need USSET  delivery time within 45days .
    Remark: The above design and specification are subject to change without prior notice for product improvement.
    Rating Conditions
    Cooling
    Indoor Temperature 27oC DB/19oC WB
    Outdoor Temperature 35oC DB/24oC WB
    Heating  ,20oC DB/15oC WB,7oC DB/6oC WB